Facility: API Manufacturing Unit
Connected Load: 18 MW
Peak Demand: ~11.5 MW
Voltage Level: 33 kV / 415 V
Distribution Network: Dual-source 33 kV input, 2 x 1600 kVA transformers, 3 main LT panels, 12 load centres
Major Loads: HVAC, chillers, reactors, centrifuges, cleanroom VFDs, lighting, packaging lines
Load Flow Analysis
Objective: Evaluate system performance during peak and normal operation.
Simulated Scenarios:
- Case A: All loads running, including HVAC (Summer)
- Case B: Critical lines only, HVAC at 50% load (Monsoon)
- Case C: Expansion scenario (10% load increase)
Findings:
- Voltage at LCP-5 dropped to 393 V (6.6% below nominal) during peak in Case A.
- Bus-2 transformer load exceeded 94% utilization, triggering thermal alarms.
- Load imbalance between phases reached up to 17%, primarily on the cleanroom loads due to single-phase machinery.
Conclusion: Without optimization, the system would not support expansion beyond 10% load increase.
Harmonic Distortion Assessment
Measurement Points:
- Panel LCP-2 (serving HVAC VFDs)
- LCP-6 (serving packaging line)
- Main LT Panel Bus-1
THD Levels (Current):
- LCP-2: 8.2% (Exceeded IEEE 519 limit of 5%)
- LCP-6: 5.7%
- Main Bus: 4.6%
Analysis:
- Source: HVAC compressors using outdated VFDs with no harmonic mitigation.
- Ripple currents caused maloperation of PLCs in packaging lines (3 instances logged in 4 weeks).
- Measured K-factor of transformers: exceeded 9. Transformers were not K-rated, increasing winding heating.
Action Suggested:
- Passive filter bank at LCP-2
- K-rated isolation transformer addition to LCP-6
Transformer Loading & Diversity Analysis
Observations:
- T1 (1600 kVA) handled 82% of load while T2 remained at 42% due to misconfigured load transfer logic.
- Night shifts (when HVAC load drops) still showed T1 at 70% due to fixed feeder routing.
Simulation Result:
- Load balancing improved voltage stability by +1.8% at downstream feeders.
- Lowered transformer hotspot temperature by 8°C after reconfiguration.
Protection Coordination & Relay Discrimination
Tools Used: ETAP 21.0
System Inputs: Breaker curves, relay settings, manufacturer datasheets, transformer impedance
Findings:
- Breaker at Packaging Line Sub-panel was rated at 10 kA, while fault current was calculated at 12.3 kA RMS – > Under-rated breaker = safety risk.
- Upstream-downstream relay curves overlapped (no time selectivity), risking full bus shutdown on local faults.
Coordination Achieved:
- Primary relays (Main Incomer) set to trip at 0.6 sec
- Downstream relays adjusted to 0.2–0.3 sec zones
- Verified minimum clearance of 0.3 sec for 3 zones
Simulation Validation:
- All faults isolated within 1 level with no upstream tripping in test model
- System achieved 100% selectivity for 95% of fault conditions
Short Circuit Analysis
Key Metrics:
- Calculated fault at Main Bus: 28.7 kA (3Ï•, symmetrical)
- Bus-4 fault: 14.2 kA
- Breaker Capacity Check: 10 feeders found with <15% margin
Conclusion: Breaker upgrades recommended for 4 feeders and 2 capacitor bank panels.
| Study Area | Pre-Audit Status | Post-Recommendation Impact |
| Voltage Drop | Up to 6.6% on peak loads | Reduced to under 2.5% |
| Transformer Loading | 98% (unbalanced) | Balanced at 72% each |
| THD Current (VFD Panels) | 8.2% | Reduced to 3.9% after filtering |
| Nuisance Tripping | 4 incidents/month | 0 incidents in 2 months post-tuning |
| Relay Discrimination | 60% zones overlapped | 100% selectivity achieved |
| Downtime | 37 hours/month | Reduced to 27 hours/month (-27%) |